搜索热:失效分析 陶瓷
扫一扫 加微信
首页 > 期刊论文 > 论文摘要
放电线圈安装于绝缘台架上外壳误接地事故分析
          
Analysis on Discharge Coil Installed on the Insulation Bench with Error Grounding

摘    要
500 kV三林变电站在对电容器充电操作时,发生1号主变3号电容器爆炸起火事故。通过分析发生事故时的保护动作报告、查看原始设计图纸以及对照现场电容器组接线,确诊3号电容器发生爆炸的主要原因,是设备安装人员将安装于绝缘台架上的电容器放电线圈外壳接地线,直接与接地铜牌相连了。为此,建议在设备安装说明书和设计图纸中,应该强调“放电线圈安装于绝缘台架上,外壳不得接地”的警示语,并提出了防止发生类似爆炸事故的技术措施。
标    签 放电线圈外壳接地   35 kV电容器爆炸   事故分析   误接线   Discharge coil grounding   Capacitor explosion   Accident analysis   Error wiring  
 
Abstract
No. 3 capacitor of San Lin substation occurred an explosion and fire accident when doing the charging operation. Analyzing on protection action report, the original design drawings and wiring of capacitor group, reason of the accident is found. That is the discharge coil installed on the insulation bench connected to the earth terminal by mistake. In this paper the settlements are proposed, such as adding the warnings to installation specifications and design drawings, and careful examination before operating.

中图分类号 X928.02

 
  购买该论文  中国光学期刊网论文下载说明


所属栏目 电力技术

基金项目

收稿日期 2014/10/21

修改稿日期

网络出版日期

作者单位点击查看

备注潘征宇(1981),男,工程师,本科,从事超高压系统变电运行工作。

引用该论文: Pan Zhengyu. Analysis on Discharge Coil Installed on the Insulation Bench with Error Grounding[J]. Power & Energy, 2014, 35(6): 729~730
潘征宇. 放电线圈安装于绝缘台架上外壳误接地事故分析[J]. 电力与能源, 2014, 35(6): 729~730


论文评价
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
分享论文
分享到新浪微博 分享到腾讯微博 分享到人人网 分享到 Google Reader 分享到百度搜藏分享到Twitter
相关信息
   标题 相关频次
 供电线路事故特征的辨识及处理
 1