Perforation Failure Analysis on Copper Pipe for Cooling Tower
摘 要
某公司所使用的冷却塔热交换器铜管在使用过程中出现了穿孔现象。对水质、铜管及产物进行了全面分析,结果表明:由于维护不当,致使所用循环水中氯离子含量过高是铜管失效的主要原因。铜管表面的腐蚀失效行为是由电化学腐蚀和化学腐蚀共同作用的结果,电化学腐蚀为主要因素,化学腐蚀次之。水中氯离子含量较高,导致铜管表面发生了电化学腐蚀,可溶性盐含量较高,促进了小孔腐蚀的发展。
Abstract
Perforation failure occurred in the copper pipes for cooling tower in use. The water, copper pipes and filth product were analyzed, and the results showed that the main failure reason was the excessive amounts of chloride ions in circulating water because of the improper maintenance. The failure was the result of electrochemical corrosion and chemical etching, and electrochemical corrosion was the main reason. The electrochemical corrosion occurred because of the excessive amounts of chloride ions and soluble salt promoted the hole corrosion.
中图分类号 TU279.7+41
所属栏目 质量控制与失效分析
基金项目
收稿日期 2014/7/19
修改稿日期
网络出版日期
作者单位点击查看
备注刘淑凤(1981-),女,工程师,硕士。
引用该论文: LIU Shu-feng,XIA Wen,ZHANG Li-min,ZUO Yu-ting. Perforation Failure Analysis on Copper Pipe for Cooling Tower[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2014, 50(11): 856~859
刘淑凤,夏雯,张丽民,左玉婷. 冷却塔铜管穿孔失效分析[J]. 理化检验-物理分册, 2014, 50(11): 856~859
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】张智强.紫铜焊接脆化原因分析[J].材料开发与应用,2005,20(5):37-39.
【2】陆辉,戴越,杨庆平,等.电厂冷油器黄铜管开裂失效分析[J].理化检验-物理分册,2009,45(增刊1):64-66.
【3】丁兆勇,王秀梅.凝汽器冷凝管的腐蚀与防护[J].中国设备工程,2007(8):56-59.
【4】黄世定,李卫.凝汽器铜管腐蚀分析及改造方案[J].应用科学,2010(8):120-121.
【5】洛阳铜加工厂中心试验室金相组.铜及铜合金金相图谱[M].北京:冶金工业出版社,1983:24-25.-
【2】陆辉,戴越,杨庆平,等.电厂冷油器黄铜管开裂失效分析[J].理化检验-物理分册,2009,45(增刊1):64-66.
【3】丁兆勇,王秀梅.凝汽器冷凝管的腐蚀与防护[J].中国设备工程,2007(8):56-59.
【4】黄世定,李卫.凝汽器铜管腐蚀分析及改造方案[J].应用科学,2010(8):120-121.
【5】洛阳铜加工厂中心试验室金相组.铜及铜合金金相图谱[M].北京:冶金工业出版社,1983:24-25.-
相关信息