Measurement of the Off Potential and Depolarization Process of Buried Pipelines with Test Block Power Interruption Method
摘 要
采用试片断电法测量管道的断电电位来评价埋地管道的阴极保护效果。在室内建立了一个埋地管道外加电流阴极保护系统, 用试片断电法测量了管道缺陷处的断电电位和去极化过程, 并对测量结果进行分析。结果表明, 断电电位应在断电后50~100 ms之间读取, 按此测量试片去极化过程中形成的电位差值, 该值与100 mV的比较结果可以判断阴极保护效果。
Abstract
The test block power interruption method is an effective way to measure the cathodic protection potential. There was a impressed-current cathodic protection system for buried pipeline in the laboratory, and the test block power interruption method was applied to test the off potential and depolarization process of the buried pipeline. The experimental results showed that the off potential should be recorded at 50~100 ms after cutting off the power supply. If the potential difference-value between the off potential and depolarized potential matches the 100 mV cathodic protection criterion, the cathodic protection is valid, otherwise the pipeline will corrode.
中图分类号 TG174.41
所属栏目 应用技术
基金项目
收稿日期 2011/5/12
修改稿日期
网络出版日期
作者单位点击查看
备注谢跃辉, 硕士研究生,
引用该论文: LI Zi-li,XIE Yue-hui,HAO Hong-na,WEI Xu,ZHANG Na,YU Hao. Measurement of the Off Potential and Depolarization Process of Buried Pipelines with Test Block Power Interruption Method[J]. Corrosion & Protection, 2012, 33(3): 255
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】彭荣, 马学峰, 黄海, 等. 断电法在管道阴极保护效果评价中的运用[J]. 腐蚀与防护, 2005, 26(10):458-460.
【2】秦莺, 宋伟, 郑志受. 辅助试片法管道阴极保护电位的精确测量[J]. 计量技术, 2008(11):35-38.
【3】黄腾飞. 埋地管道阴极保护电位参数及电位测试技术研究[D]. 南充: 西南石油学院, 2004.
【4】翁永基, 阎茂成, 李相怡. 断电法消除管道阴极保护电位IR降的研究[J]. 油气储运, 2002, 21(5):30-34.
【5】胡士信, 熊信勇, 石薇, 等. 埋地钢质管道阴极保护真实电位的测量技术[J]. 腐蚀与防护, 2005, 26(7):297-301.
【2】秦莺, 宋伟, 郑志受. 辅助试片法管道阴极保护电位的精确测量[J]. 计量技术, 2008(11):35-38.
【3】黄腾飞. 埋地管道阴极保护电位参数及电位测试技术研究[D]. 南充: 西南石油学院, 2004.
【4】翁永基, 阎茂成, 李相怡. 断电法消除管道阴极保护电位IR降的研究[J]. 油气储运, 2002, 21(5):30-34.
【5】胡士信, 熊信勇, 石薇, 等. 埋地钢质管道阴极保护真实电位的测量技术[J]. 腐蚀与防护, 2005, 26(7):297-301.
相关信息