Influence of Stray Current on Corrosion in Substation Grid
摘 要
采用土壤电位梯度法和管地电位连续监测法, 测试了500kV超高压变电站内杂散电流的干扰强度, 结果表明变电站内有不超过中等强度的杂散电流, 同时, 杂散电流与变电站电压等级没有明显相关性, 而与变电站内电气设备的运行状况、电气装置的设计安装等因素相关。
Abstract
Stray current in an ultra high voltoge(UHV) substation was monitored by the detection technique of soil voltage gradient and continuous monitoring of pipe-soil potential. The results show that the effect of stray current was in moderate intensity. The results also indicated that the stray current was not related to the voltage classes of the substation, but to the running status, design and install technology of electrical equipments.
中图分类号 TG174
所属栏目 应用技术
基金项目
收稿日期 2012/1/11
修改稿日期
网络出版日期
作者单位点击查看
联系人作者李建华(oldli31@163.com)
备注李建华,高级工程师,硕士,
引用该论文: LI Jian-hua,ZHENG Min-cong,NIE Xin-hui. Influence of Stray Current on Corrosion in Substation Grid[J]. Corrosion & Protection, 2012, 33(9): 804