Effects of Cathode Polarization on Stree Corrosion Behavior of HRB335 Reinforcing Steel Bar
摘 要
采用慢应变速率试验(SSRT)与阴极极化电位相结合的方法,研究了阴极极化对HRB335钢筋在模拟服役环境中腐蚀行为的影响。结果表明,当阴级极化电位为-475~-850 mVCSE时,钢筋存在一定的应力腐蚀敏感性; 当电位负于-1 200 mVCSE时,钢筋发生氢致应力腐蚀开裂。对于HRB335钢筋混凝土体系施加阴极保护时,作为阴极保护的有效判据,建议采用-1 000~-1 100 mVCSE的阴极极化电位。
Abstract
The effects of cathodic polarization on the stress corrosion behavior of HRB335 reinforcing steel bar in simulated concrete pore solution were studied by slow strain rate test (SSRT) and cathodic polarization. The results show that when the polarization potential was between -475 mVCSE and -850 mVCSE, the steel bar exhibited certain stress corrosion sensitivity. And when the polarization potential was below -1 200 mVCSE, hydrogen induced stress cracking occured. For effective cathodic protection in reinforced concrete system, a polarization potential criterion between -1 000 mVCSE and -1 100 mVCSE is recommended.
中图分类号 TG174.1
所属栏目 试验研究
基金项目
收稿日期 2012/9/12
修改稿日期
网络出版日期
作者单位点击查看
备注曹备,副教授,博士,
引用该论文: YANG Jiang,CAO Bei,WU Yin-shun,HE Hong-wei,YANG Tao. Effects of Cathode Polarization on Stree Corrosion Behavior of HRB335 Reinforcing Steel Bar[J]. Corrosion & Protection, 2013, 34(8): 693
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】姚武,徐晶. 钢筋混凝土阴极保护体系中的电流分布[J]. 同济大学学报,2009,37(8):1014-1018.
【2】朱雅仙,蔡伟成. PCCP高强钢丝阴极保护准则的试验研究[J]. 水利水运工程学报,2010,20(6):34-38.
【3】黄永昌. 电化学保护技术及其应用[J]. 腐蚀与防护,2000,21(10):471-475.
【4】闫茂成,翁永基,王俭秋. 研究电化学充氢过程中X70钢氢吸收的新方法[J]. 材料研究学报,2007,21(4):343-347.
【2】朱雅仙,蔡伟成. PCCP高强钢丝阴极保护准则的试验研究[J]. 水利水运工程学报,2010,20(6):34-38.
【3】黄永昌. 电化学保护技术及其应用[J]. 腐蚀与防护,2000,21(10):471-475.
【4】闫茂成,翁永基,王俭秋. 研究电化学充氢过程中X70钢氢吸收的新方法[J]. 材料研究学报,2007,21(4):343-347.
相关信息