Causes and Treatment Scheme of Tower Foot Corrosion of a 500kV Transmission Tower
摘 要
对某500kV输电线路铁塔塔脚出现严重腐蚀的现场宏观检查,对上底座腐蚀产物取样进行XRD,SEM和EDS分析。结果表明,塔脚的腐蚀是发生在上底座和护板表面的局部腐蚀,主要是大气中SO2对塔脚造成的腐蚀。塔脚所处的位置SO2浓度最高,而锌和A3钢在SO2存在的条件下,腐蚀速率都高于在纯空气中(不含SO2),生成的腐蚀产物结构多孔疏松,且铁塔经常处于潮湿条件下的服役环境能够满足腐蚀持续进行的电化学条件。这些因素共同作用,导致塔脚的腐蚀速率很高,在1~2a的时间内腐蚀减薄已达50%。根据对腐蚀原因的分析,制定了相应的焊补加固和防腐蚀涂料体系方案。
Abstract
The causes of severe corrosion of a 500kV transmission tower foot were analyzed and a fix scheme wasformulated.The results of macro inspection,SEM,EDS and XRD analyses of corrosion products sampled from abovepedestal show that the corrosion of tower foot occurring on the pedestal and protective plate surface was localizedcorrosion.The mainly reason was SO2in atmosphere.The position of tower foot had the highest concentration ofSO2.Because of the existence of SO2,the corrosion rate was much higher than that of in the pure air.The structureof corrosion products was porous and service environment was in moist condition,which met the conditions ofelectrochemical corrosion continuous development.These factors worked together and led to a very high corrosion rateof tower foot,the corrosion thinning reached 50% within 1~2a.Thus a welding repair and anticorrosive coatingsystem of corresponding solution was formulated.
中图分类号 TG174
所属栏目 应用技术
基金项目
收稿日期 2013/1/4
修改稿日期
网络出版日期
作者单位点击查看
联系人作者刘爽(gigihou@sina.com)
备注刘爽,工程师,硕士,
引用该论文: LIU Shuang,HU Xin-fang,GAO Sen,FAN Zhi-bin. Causes and Treatment Scheme of Tower Foot Corrosion of a 500kV Transmission Tower[J]. Corrosion & Protection, 2013, 34(11): 1026
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】何长华.输电线路铁塔用钢的发展趋势[J].电力建设,2010,31(1):45-48.
【2】陈云,强春媚,王国刚,等. 输电铁塔的腐蚀与防护[J].电力建设,2010,31(8):55-58.
【3】Pareja R R,Ibaneg R L,Martin F,et al.Corrosion be-havior of zirconia′s barrier coatings on galvanized steel[J].Surface & Coatings Technology,2006,200:6606-6610.
【4】Shibli S M A,Jayalekshmi A C,Remya R.Electro-chemical and structural characterization of the mixedoxides-reinforced hot-dip zinc coating[J].Surface &Coatings Technology,2007,201:7560-7565.
【5】Bastos A C,Ferreia M U S,Simoea A M.Comparativeelectrochemical studies of zinc chromate and zinc phos-phate as corrosion inhibitors for zinc[J].Progress inOrganic Coatings,2005,52:339-350.
【6】Aramaki K.The inhibition effects of chromate-free,anion inhibitors on corrosion of zinc in aerated 0.5 MNaCl[J].Corrosion Science,2001,43:591-604.
【7】梁彩凤,侯文泰.环境因素对钢的大气腐蚀的影响[J].中国腐蚀与防护学报,1998,18(1):1-6.
【8】Arroyave C,Lopez F Z,Morcillo M.The early atmos-pheric corrosion stages of carbon steel in acidic fogs[J].Corrosion Science,1995,37(11):1751-1761.
【2】陈云,强春媚,王国刚,等. 输电铁塔的腐蚀与防护[J].电力建设,2010,31(8):55-58.
【3】Pareja R R,Ibaneg R L,Martin F,et al.Corrosion be-havior of zirconia′s barrier coatings on galvanized steel[J].Surface & Coatings Technology,2006,200:6606-6610.
【4】Shibli S M A,Jayalekshmi A C,Remya R.Electro-chemical and structural characterization of the mixedoxides-reinforced hot-dip zinc coating[J].Surface &Coatings Technology,2007,201:7560-7565.
【5】Bastos A C,Ferreia M U S,Simoea A M.Comparativeelectrochemical studies of zinc chromate and zinc phos-phate as corrosion inhibitors for zinc[J].Progress inOrganic Coatings,2005,52:339-350.
【6】Aramaki K.The inhibition effects of chromate-free,anion inhibitors on corrosion of zinc in aerated 0.5 MNaCl[J].Corrosion Science,2001,43:591-604.
【7】梁彩凤,侯文泰.环境因素对钢的大气腐蚀的影响[J].中国腐蚀与防护学报,1998,18(1):1-6.
【8】Arroyave C,Lopez F Z,Morcillo M.The early atmos-pheric corrosion stages of carbon steel in acidic fogs[J].Corrosion Science,1995,37(11):1751-1761.