Analysis on Fracture Reason of 35 kV Casing Pipe Wire Clamp
摘 要
通过对某供电公司下属变电站主变35 kV断裂套管线夹进行化学成分分析、金相检验、硬度检验、扫描电镜及能谱分析,结合该套管线夹断裂的位置和方式,综合分析了该线夹断裂的原因.结果表明:材料内部含有过多的增加虚拟锌含量的合金元素并且以大尺寸球形夹杂物的形式存在于基体中,部分以颗粒状及长条状分布于α相晶界,导致线夹脆性增加,力学性能降低,在线夹结构薄弱处发生了断裂.
Abstract
The comprehensive analysis on fracture reason of 35 kV casing pipe wire clamp in a main transformer substation of a power supply company by means of chemical composition analysis,metallographic examination,hardness testing,SEM and energy spectrum analysis,combined with the fracture position and fracture mode of wire clamp.The results showed that too much alloy elements increased the virtual zinc content in the form of the large-size spherical inclusions distributed in the matrix,and the granular and elongated portion located in the α phase grain boundaries,leading to the increased brittleness and the decreased mechanical performance of wire clamp,at last the fracture occurred in the structure weaknesses of wire clamp.
中图分类号 TM64 DOI 10.11973/lhjy-wl201507019
所属栏目 质量控制与失效分析
基金项目
收稿日期 2014/10/23
修改稿日期
网络出版日期
作者单位点击查看
备注武家升(1982-),男,工程师.
引用该论文: WU Jia-sheng,LIU Liang,LI Peng. Analysis on Fracture Reason of 35 kV Casing Pipe Wire Clamp[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2015, 51(7): 517~519
武家升,刘亮,李朋. 35kV套管线夹断裂原因分析[J]. 理化检验-物理分册, 2015, 51(7): 517~519
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】DL/T 991-2006电力设备金属光谱分析技术导则[S].
【2】李炯辉.金属材料金相图谱[M].北京:机械工业出版社,2006.
【3】张博.金相检验[M].北京:机械工业出版社,2009.
【4】丁惠麟,辛智华.实用铝,铜合金金相热处理和失效分析[M].北京:机械工业出版社,2008.
【2】李炯辉.金属材料金相图谱[M].北京:机械工业出版社,2006.
【3】张博.金相检验[M].北京:机械工业出版社,2009.
【4】丁惠麟,辛智华.实用铝,铜合金金相热处理和失效分析[M].北京:机械工业出版社,2008.
相关信息