Leak Testing for Manufacturing and Shutdown of Nuclear Power Station Steam Generator
摘 要
介绍了核电站蒸汽发生器制造时管子与管板焊缝的氦检漏技术和检测一、二次侧间总泄漏率的方法。在核电站停堆期间的氦检漏和水分检漏的方法, 已成功地在坎杜堆蒸汽发生器中采用, 氦检漏和水分检漏技术的检测限值分别为0.001和0.05 kg/h。
Abstract
Introduced the helium leak testing technologies of welded joint tube-to-tubesheet for steam generator manufacturing and method of all leakage rate monitoring of secondary-to-primary side were introduced. The helium leak testing and water content leak testing were used successfully for shutdown in CANDU steam generators, and their detection limits were 0.001 and 0.005 kg/h, respectively.
中图分类号 TG115.28
所属栏目 实践经验
基金项目
收稿日期 2008/4/3
修改稿日期
网络出版日期
作者单位点击查看
备注丁训慎(1936-), 男, 教授级高工, 主要从事核电站蒸汽发生器的设计、研究和在役检查工作。发表论文160篇, 曾获部级科技成果奖二等奖2项, 三等奖3项, 申报国家专利技术2项。
引用该论文: DING Xun-Shen. Leak Testing for Manufacturing and Shutdown of Nuclear Power Station Steam Generator[J]. Nondestructive Testing, 2009, 31(2): 159~161
丁训慎. 核电站蒸汽发生器制造和停堆期间的泄漏检验[J]. 无损检测, 2009, 31(2): 159~161
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】周寿康.核蒸汽发生器氦气检漏技术[J].核动力运行研究,1993,6(2):50.
【2】李华纲, 唐伟宝.秦山二期核电蒸汽发生器管子与管板液压胀管[J].核电工程与技术,2004,17(3):28.
【3】丁训慎.坎杜型核电站蒸汽发生器的检查和维修[J].核动力运行研究,1997,10(2):11.
【4】Maynard K J, Singh V P. Leak testing of CANDU steam generator[C]. Steam Generator and Heat Exchanger Conference. Toronto:1998.《无损检测》邮发代号: 4-237, 欢迎订阅!