Leakage Reason Analysis of High Temperature Reheater Tube of Circulating Fluidized Bed Boiler
摘 要
通过宏观和微观检验对某循环流化床锅炉一段焊接有螺柱的高温再热器管水压试验时泄漏的原因进行了分析。结果表明: 泄漏是由连多硫酸应力腐蚀造成的,并指出循环流化床锅炉受热面不锈钢管利用螺柱焊焊接锚固件的工艺值得进一步探讨。
Abstract
Leakage reason of a high temperature reheater tube of a circulating fluidized bed boiler during water pressure test was investigated by means of macroscopic and microscopic examination. The results showed that the cracks were induced by polythionic acid stress corrosion. It was indicated that the stud welding of anchors on stainless steel tube was questionable.
中图分类号 TK223.1+1 TK229
所属栏目 质量控制与失效分析
基金项目
收稿日期 2009/9/23
修改稿日期
网络出版日期
作者单位点击查看
备注胡 平(1973-),女,博士。
引用该论文: HU Ping,DONG Zhong-li. Leakage Reason Analysis of High Temperature Reheater Tube of Circulating Fluidized Bed Boiler[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2010, 46(7): 462~464
胡 平,董重里. 循环流化床锅炉高温再热器管泄漏原因分析[J]. 理化检验-物理分册, 2010, 46(7): 462~464