Failure Analysis of Bursted Water Screen Tubes of Boiler
摘 要
采用宏观检验、力学性能检测、金相检验、扫描电镜检查和X射线衍射分析等方法对某锅炉水冷壁管发生爆管的原因进行了分析。结果表明:水冷壁管爆裂是由于酸泄漏事故引起的,泄漏导致接触烟气侧的管内壁存在较多细小的微裂纹,使材料的拉伸强度和屈服强度大幅降低,加上锅炉水系统漏入酸溶液引起了氢腐蚀,最终导致水冷壁管在工作应力下发生氢脆断裂。
Abstract
A failure accident of water screen tubes of boiler had been analyzed. Visual examination,mechanical test,metallographic examination,electron scanning microscope examination,X-ray diffraction examination had been used for this analysis. Lots of fine-cracks had been found on the inside wall of water screen tubes towards the fume. Deeply decrease of tensile strength and yield strength had been found when the water screen tubes towards the fume. The PH value of this boiler’s water system was out of control as acidic property,which was caused by a mistake of operation in the past time. Hydrogen brittle fracture had been confirmed as the reason of the fracture of water screen tubes.
中图分类号 TK223.3+1
所属栏目 质量控制与失效分析
基金项目 “十一五”国家科技支撑计划资助项目,(2006BAK02B03)
收稿日期 2008/12/26
修改稿日期
网络出版日期
作者单位点击查看
备注姜海一(1977-),男,工程师,硕士。
引用该论文: JIANG Hai-yi,DOU Wen-yu,JIA Guo-dong,DU Chen-yang,LI Shuo-yu,GAO Guan-long. Failure Analysis of Bursted Water Screen Tubes of Boiler[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2009, 45(12): 768~772
姜海一,窦文宇,贾国栋,杜晨阳,李硕煜,高官龙. 锅炉水冷壁管爆管原因分析[J]. 理化检验-物理分册, 2009, 45(12): 768~772
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】周昊,池作合. 根据爆口特征判断爆管原因[J]. 热力发电,1999(5):43-45.
【2】李艳萍,岳增武,洪景娥. 240 t/h锅炉水冷壁爆管原因分析[J].腐蚀科学与防护技术,2008,20(3):190-192.
【3】李风瑞,池作和,周昊,等.大容量锅炉锅内腐蚀爆管的特点及对策[J]. 锅炉技术,1998(10):25-27.
【2】李艳萍,岳增武,洪景娥. 240 t/h锅炉水冷壁爆管原因分析[J].腐蚀科学与防护技术,2008,20(3):190-192.
【3】李风瑞,池作和,周昊,等.大容量锅炉锅内腐蚀爆管的特点及对策[J]. 锅炉技术,1998(10):25-27.
相关信息