Reason Analysis on Fracture of Reinforced Concrete Poles
摘 要
某变电站两根钢筋混凝土电杆突然断裂倒塌,造成变压器及相关设备损坏。采用宏观检查、卵石粒径和螺旋筋尺寸测量、预应力筋质量测量、力学性能测试、化学成分分析等方法,对钢筋混凝土电杆的断裂原因进行了分析。结果表明:预应力筋的抗拉强度、屈服强度、质量和化学成分不合格等严重的质量问题,以及电杆在施工安装过程中埋深不足,是导致电杆断裂失效的主要原因。
Abstract
Two reinforced concrete poles in one substation fractured and collapsed suddenly, causing damage to the transformer and related equipments. Fracture reasons of reinforced concrete poles were analyzed by macro observation, measurement of cobblestone diameter and dimension of spiral steel bars, weigh measurement, mechanical property testing, chemical composition analysis of prestressing tendons and so on. The results show that:the serious quality problems such as disqualification of tensile strength, yield strength, weight and chemical compositions of prestressing tendons, and insufficient installation depth of the poles in the construction process gave rise to the fracture failure of the poles.
中图分类号 TU757 DOI 10.11973/lhjy-wl201711014
所属栏目 质量控制与失效分析
基金项目
收稿日期 2017/2/25
修改稿日期
网络出版日期
作者单位点击查看
备注熊亮(1983-),男,高级工程师,硕士,主要从事材料失效原因分析、寿命评价方面的研究,abcd4858@163.com
引用该论文: XIONG Liang,WAN Keyang,LIU Jiaojiao,CAO Zhi. Reason Analysis on Fracture of Reinforced Concrete Poles[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2017, 53(11): 826~828
熊亮,万克洋,刘蛟蛟,曹智. 钢筋混凝土电杆断裂原因分析[J]. 理化检验-物理分册, 2017, 53(11): 826~828
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】徐乃欣. 钢筋混凝土电杆的腐蚀及防护[J].腐蚀与防护,2000,21(11):509-510.
【2】GB/T 4623-2014 环形混凝土电杆[S].
【3】GB/T 5223-2002 预应力混凝土用钢丝[S].
【4】YB/T 146-1998 预应力钢丝及钢绞线用热轧盘条[S].
【5】CECS 02:2005 超声回弹综合法检测混凝土强度技术规程[S].
【2】GB/T 4623-2014 环形混凝土电杆[S].
【3】GB/T 5223-2002 预应力混凝土用钢丝[S].
【4】YB/T 146-1998 预应力钢丝及钢绞线用热轧盘条[S].
【5】CECS 02:2005 超声回弹综合法检测混凝土强度技术规程[S].
相关信息