Cause Analysis on Fracture of Transmission Wire
摘 要
某500 kV输电导线在架线施工过程中发生断裂,通过宏观观察、几何尺寸检测、化学成分分析、力学性能试验、断口形貌宏微观分析、模拟试验等方法对导线的断裂原因进行了分析。结果表明:导线结构尺寸、力学性能及材料正常;断口均为典型的正向拉断断口,未发现原有缺陷;通过设计导线的逐层拉断试验及现场力学条件的模拟试验,发现导线在加载至紧线器额定载荷时并未发生滑移及断裂,在接近导线额定拉断力时整体断裂,对比试样与现场断裂导线的断口形貌,确定导线是在施工过程中严重过载,于紧线器夹持位置发生逐层断裂。
Abstract
A 500 kV transmission wire fractured during the construction process. The reasons of the fracture were analyzed by macroscopic observation, geometric size detection, chemical composition analysis, mechanical property test, fracture surface macro and micro analysis, simulation test and so on. The results show that the structure size, mechanical property and material of the wire were normal, the fracture was the typical forward tensile fracture, and no defects were found. Through the design of the wire layer-by-layer tensile test and the simulation test of the field mechanical condition, it was found that the wire did not slip and fracture when the tightener was loaded to the rated load, and the whole fracture happened when the load was close to the rated pulling force of the wire. In comparison with the fracture morphology of the specimen and the fractured wire, it was determined that the wire was overloaded in the construction process, layer-by-layer fracture occured at the clamping position of the tightener.
中图分类号 TG115 DOI 10.11973/lhjy-wl201805009
所属栏目 质量控制与失效分析
基金项目
收稿日期 2017/9/25
修改稿日期
网络出版日期
作者单位点击查看
备注周静波(1985-),女,工程师,主要从事电网金属材料品质控制、失效分析及电力设备全生命周期管理等工作,25621011@qq.com
引用该论文: ZHOU Jingbo,XU Hongwei,LI Zhixiang,YANG Yingchun. Cause Analysis on Fracture of Transmission Wire[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2018, 54(5): 343~347
周静波,许宏伟,李志翔,杨迎春. 输电导线断裂原因分析[J]. 理化检验-物理分册, 2018, 54(5): 343~347
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】刘通, 代洲,王颂. 架空输电线路的故障模式及相关故障树分析[J]. 南方电网技术,2013,7(6):108.
【2】李陈. 简要探索500 kV线路工程紧线及平衡挂线施工思路构架[J]. 中国新技术新产品,2014,11(22):95-96.
【3】王荣. 机械装备的失效分析(续前)第3讲断口分析技术(下)[J]. 理化检验(物理分册),2016,52(10):833-840.
【4】杨瑞成,杨钒. 失效分析与选材[M]. 上海:上海交通大学出版社,2014.
【5】陈群. 电力输电线路架线施工技术的应用分析[J]. 通讯世界,2014,12(23):69-70.
【2】李陈. 简要探索500 kV线路工程紧线及平衡挂线施工思路构架[J]. 中国新技术新产品,2014,11(22):95-96.
【3】王荣. 机械装备的失效分析(续前)第3讲断口分析技术(下)[J]. 理化检验(物理分册),2016,52(10):833-840.
【4】杨瑞成,杨钒. 失效分析与选材[M]. 上海:上海交通大学出版社,2014.
【5】陈群. 电力输电线路架线施工技术的应用分析[J]. 通讯世界,2014,12(23):69-70.
相关信息