Cause Analysis on Fracture of DN25 Copper Valve for a Heating Pipe Network
摘 要
某供热管网用DN25铜阀安装2个月后出现阀体断裂现象,采用宏观分析、化学成分分析、断口分析、金相检验、硬度测试等方法对铜阀的断裂原因进行了分析。结果表明:该铜阀壁厚偏薄,在水中氯离子和工作应力的共同作用下发生了应力腐蚀开裂,最终断裂失效。
Abstract
The fracture of the valve body occurred after DN25 copper valve being installed in a heating pipe network for 2 months. The fracture causes of the copper valve were analyzed by means of macroscopic analysis, chemical composition analysis, fracture analysis, metallographic examination, hardness test and so on. The results show that the wall thickness of the copper valve was thin, and stress corrosion cracking occured under the combined action of chloried in the water and working stress, which eventually led to the fracture of the copper valve.
中图分类号 TG115.5 TG146.1 DOI 10.11973/lhjy-wl201905018
所属栏目 质量控制与失效分析
基金项目
收稿日期 2018/7/12
修改稿日期
网络出版日期
作者单位点击查看
备注吴文祥(1980-),男,工程师,博士,主要从事金属构件的失效分析研究,wwx985@163.com
引用该论文: WU Wenxiang,FANG Shaolin. Cause Analysis on Fracture of DN25 Copper Valve for a Heating Pipe Network[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2019, 55(5): 356~358
吴文祥,方少林. 某供热管网用DN25铜阀断裂原因分析[J]. 理化检验-物理分册, 2019, 55(5): 356~358
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】陈彩霞,郑杨艳. 空调水铜阀断裂原因分析及预防[J]. 金属热处理,2015,40(1):204-207.
【2】郭亮,金献忠,黄世杰,等. 铅黄铜阀芯部件开裂分析[J]. 理化检验(物理分册),2013,49(9):625-627.
【3】莫明珍,谭莹,郭春文,等. 铜阀应力腐蚀开裂分析[J]. 热加工工艺,2014,43(6):213-214.
【4】曹标,谭莹,李小敏. 黄铜角阀开裂原因分析[J]. 理化检验(物理分册),2017,53(11):841-843.
【5】张栋,钟培道,陶春虎,等. 失效分析[M]. 北京:国防工业出版社,2004.
【6】高进,孙金厂. 金属材料应力腐蚀失效分析[J]. 山东轻业学院学报,2001,15(1):47-50.
【2】郭亮,金献忠,黄世杰,等. 铅黄铜阀芯部件开裂分析[J]. 理化检验(物理分册),2013,49(9):625-627.
【3】莫明珍,谭莹,郭春文,等. 铜阀应力腐蚀开裂分析[J]. 热加工工艺,2014,43(6):213-214.
【4】曹标,谭莹,李小敏. 黄铜角阀开裂原因分析[J]. 理化检验(物理分册),2017,53(11):841-843.
【5】张栋,钟培道,陶春虎,等. 失效分析[M]. 北京:国防工业出版社,2004.
【6】高进,孙金厂. 金属材料应力腐蚀失效分析[J]. 山东轻业学院学报,2001,15(1):47-50.
相关信息