Cause of Fracture on Suspension Clamp of a 220 kV Transmission Line
摘 要
某220 kV输电线路XGF-6X型ZL102铝合金悬垂线夹在运行中发生断裂,通过宏观分析、化学成分分析、硬度测试、机械破坏载荷测试、射线检测、断口分析等方法对悬垂线夹的断裂原因进行了分析。结果表明:悬垂线夹的尺寸不符合设计要求,且悬垂线夹的内部存在气孔、夹渣等铸造缺陷,使得悬垂线夹的机械破坏载荷低于标准的要求,运行中由于覆冰导致悬垂线夹垂直载荷增大,最终发生过载断裂。
Abstract
The XGF-6X ZL102 aluminum alloy suspension clamp of a 220 kV transmission line fractured during operation. The causes of fracture on suspension clamp were analyzed by means of macro analysis, chemical composition analysis, hardness test, mechanical failure load test, radiographic inspection and fracture analysis.The results show that the size of suspension clamp did not meet the design requirements, and there were some casting defects such as pores and slag inclusions in suspension clamp, which made the mechanical failure load of suspension clamp lower than the standard requirements. During operation, the vertical load of suspension clamp increased due to icing, and finally overload fracture occurred.
中图分类号 TM241 TM203 DOI 10.11973/lhjy-wl202107011
所属栏目 质量控制与失效分析
基金项目 云南电网科技项目(YNKJXM20180175)
收稿日期 2020/7/29
修改稿日期
网络出版日期
作者单位点击查看
备注杨迎春(1976-),男,高级工程师,主要从事金属材料工程和无损检测工作,kmyyc@126.com
引用该论文: YANG Yingchun,YU Hongjiang,DAI Keshun. Cause of Fracture on Suspension Clamp of a 220 kV Transmission Line[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2021, 57(7): 48~51
杨迎春,虞鸿江,代克顺. 某220 kV输电线路悬垂线夹断裂原因[J]. 理化检验-物理分册, 2021, 57(7): 48~51
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】包博, 王婉婷.输电线路悬垂线夹电磁损耗的有限元分析及结构优化[J].电力建设,2012,33(11):82-85.
【2】王习武,薛志方.基于有限元法的悬垂线夹力学性能分析[J].水电能源科学,2011,29(11):171-174.
【3】王瑞科,鲍迁,张继育,等.几种常用悬垂线夹性能及节能比较[J].中国电力,2004,37(9):61-63.
【4】刘纯,唐远富,欧阳克俭,等.±800 kV输电线路预绞式悬垂线夹断裂分析[J].湖南电力, 2017,37(2):46-50.
【5】屈直,李志翔,焦宗寒.悬垂线夹金具力学性能试验工装优化[J].理化检验(物理分册),2020,56(11):1-6.
【6】施勇.龙石Ⅱ线架空地线悬垂线夹断裂事故分析[J].青海电力,2008,27(增刊):31-34.
【7】王肃,李相栋.500 kV地线悬垂线夹挂轴磨损原因分析[J].电力安全技术,2020,22(3):32-34.
【8】洪毅成,蔡建宾.220 kV输电线路悬垂金具直角挂板断裂原因分析[J].理化检验(物理分册),2017,53(5):361-364.
【9】汪军,温芝香.国外对压力容器焊缝中气孔与夹渣危害性的研究[J].化工管理,2018(27):42-43.
【10】罗宏建,龚卓,王炯耿,等.铝合金设备线夹失效分析[J].云南师范大学学报(自然科学版),2018,38(5):44-48.
【2】王习武,薛志方.基于有限元法的悬垂线夹力学性能分析[J].水电能源科学,2011,29(11):171-174.
【3】王瑞科,鲍迁,张继育,等.几种常用悬垂线夹性能及节能比较[J].中国电力,2004,37(9):61-63.
【4】刘纯,唐远富,欧阳克俭,等.±800 kV输电线路预绞式悬垂线夹断裂分析[J].湖南电力, 2017,37(2):46-50.
【5】屈直,李志翔,焦宗寒.悬垂线夹金具力学性能试验工装优化[J].理化检验(物理分册),2020,56(11):1-6.
【6】施勇.龙石Ⅱ线架空地线悬垂线夹断裂事故分析[J].青海电力,2008,27(增刊):31-34.
【7】王肃,李相栋.500 kV地线悬垂线夹挂轴磨损原因分析[J].电力安全技术,2020,22(3):32-34.
【8】洪毅成,蔡建宾.220 kV输电线路悬垂金具直角挂板断裂原因分析[J].理化检验(物理分册),2017,53(5):361-364.
【9】汪军,温芝香.国外对压力容器焊缝中气孔与夹渣危害性的研究[J].化工管理,2018(27):42-43.
【10】罗宏建,龚卓,王炯耿,等.铝合金设备线夹失效分析[J].云南师范大学学报(自然科学版),2018,38(5):44-48.
相关信息