Reason of Failure of Soft Connection of Disconnector in a 500 kV Substation
摘 要
某500 kV变电站投运仅1 a,其水平折臂式隔离开关的软连接最外层铜箔发生了断裂而失效,通过宏观观察、化学成分分析、力学性能试验和断口分析等方法,分析了铜箔断裂的原因。结果表明:铜箔与铜板过渡位置被压裂,铜箔硬度高,抗拉强度高,延伸率低,韧性差,隔离开关工作中软连接需要反复折弯,最终导致铜箔断裂,而使软连接失效。
Abstract
In a 500 kV substation, the outermost copper foil of soft connection of the horizontal knuckle-arm disconnector that was put into operation for only 1 year was broken and failed. Through macroscopic observation, chemical composition analysis, mechanical performance test and fracture analysis, the reasons for copper foil fracture were analyzed. The results showed that fracturing occurred at transition position of copper foil and copper plate, copper foil had high hardness, high tensile strength, low elongation and poor toughness. Soft connection needed to be repeatedly bent during disconnector work, which eventually led to copper foil fracture, and the soft connection was failed.
中图分类号 TG14 DOI 10. 11973/lhjy-wl202111008
所属栏目 质量控制与失效分析
基金项目
收稿日期 2020/12/17
修改稿日期
网络出版日期
作者单位点击查看
备注焦宗寒(1990-),男,工程师,主要从事电网重要部件失效分析的工作,1207962456@qq.com
引用该论文: JIAO Zonghan,YU Hongjiang,DAI Keshun. Reason of Failure of Soft Connection of Disconnector in a 500 kV Substation[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2021, 57(11): 30~32
焦宗寒,虞鸿江,代克顺. 某500 kV变电站隔离开关软连接失效的原因[J]. 理化检验-物理分册, 2021, 57(11): 30~32
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】钟振蛟. 户外隔离开关机械故障的起因及预防[J]. 高压电器, 2006, 42(6):464-467.
【2】胡红光.隔离开关触头结构与发热原因分析[J]. 高电压技术, 2001, 27(5):72-75.
【3】崔景春, 袁大陆, 宋杲.高压隔离开关运行分析及其完善化[J]. 电器工业, 2007(2):51-56.
【4】盛明学, 王志清.户外高压隔离开关常见故障的原因分析与处理[J]. 高压电器, 2010, 46(10):93-96.
【5】丁昌国.隔离开关存在的问题及改进措施[J]. 吉林电力, 2004, 32(6):55-56.
【2】胡红光.隔离开关触头结构与发热原因分析[J]. 高电压技术, 2001, 27(5):72-75.
【3】崔景春, 袁大陆, 宋杲.高压隔离开关运行分析及其完善化[J]. 电器工业, 2007(2):51-56.
【4】盛明学, 王志清.户外高压隔离开关常见故障的原因分析与处理[J]. 高压电器, 2010, 46(10):93-96.
【5】丁昌国.隔离开关存在的问题及改进措施[J]. 吉林电力, 2004, 32(6):55-56.