Analysis and Measures of Sympathetic Inrush Cause Protection Equipment Misoperation
摘 要
通过采用波形对比法, 查找和分析发电机差动保护误动的故障原因。介绍了和应涌流产生的机理、特征和非周期分量对电流互感器(TA)暂态饱和的影响。通过切磋减小或消除和应涌流对策的不同观点, 结合现场实际, 将发电机差动保护整定值由0.09 pu调整至0.25 pu, 并对二次回路负载阻抗、TA伏安特性进行试验, 检验TA伏安特性、TA精度和二次回路负载能否满足误差要求, 用以减小系统突变时和应涌流对相邻设备继电保护装置的误动。
Abstract
Cause Analysis on the misoperation of Generator Differential Protection by means of comparing with wave form. Introduce the principle and features of sympathetic inrush, influence of non-periodic components on transient saturation of current transformer. Through the different view on reducing the sympathetic inrush and actual onsite, adjust Generator Differential Protection setting from 0.09pu to 0.25pu, and test the secondary circuit load impedance and Volt-Ampere Characteristic. Through Inspecting TA Volt-Ampere Characteristic、the accuracy of TA、the secondary circuit load to meet the error requirement, reduce the misoperation of neighbor protection equipment by sympathetic inrush when system happen sudden change.
中图分类号 TM774
所属栏目 成果与经验
基金项目
收稿日期 2012/4/1
修改稿日期
网络出版日期
作者单位点击查看
备注张明(1972-),男, 电气主管, 大专, 从事电厂继电保护与电力工程技术工作。
引用该论文: Zhang Ming. Analysis and Measures of Sympathetic Inrush Cause Protection Equipment Misoperation[J]. Power & Energy, 2012, 33(3): 289~291
张明. 和应涌流对继电保护误动的分析及对策[J]. 电力与能源, 2012, 33(3): 289~291
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】毕大强, 孙叶, 李德佳, 王祥珩, 等.变压器中性点接地方式对和应涌流产生的影响分析[J].继电器,2007, 35(20).
【2】王维俭.发电机变压器继电保护应用[M].北京: 中国电力出版社,2004.
【3】许云雅.变压器励磁涌流与和应涌流的分析研究[J].华北电力大学学报,2008,35(20).
【4】李艳鹏,侯启方,刘承志.非周期分量对电流互感器暂态饱和的影响[J].电力自动化,2008,26(8).
【2】王维俭.发电机变压器继电保护应用[M].北京: 中国电力出版社,2004.
【3】许云雅.变压器励磁涌流与和应涌流的分析研究[J].华北电力大学学报,2008,35(20).
【4】李艳鹏,侯启方,刘承志.非周期分量对电流互感器暂态饱和的影响[J].电力自动化,2008,26(8).
相关信息