Impact of UHV DC Transmission AC Filter Detuning Protect the Accuracy of the Analysis
摘 要
锦苏±800 kV特高压直流输电苏州站投运过程中,发生失谐保护频繁发信事件,通过对失谐保护原理、保护逻辑、动作过程等深度分析,指出6次谐波分量的影响是主要原因。提出在建设特高压直流输电换流站时,需要吸取失谐保护频繁发信事件的教训,实时检测交流系统谐波电压状况,紧密监视直流偏磁对电网的影响,排查隐患消除缺陷。建议针对失谐保护频繁发信案例,深入研究换流变充电励磁涌流对交流系统谐波的影响。
Abstract
JinSu±800kV UHV DC transmission process Su Zhou station was put into operation, detuning protection frequently transmitting incidents, through to the detuning protection principle, protection logic, action process etc depth analysis, points out the influence of six times harmonic is the main reason. Put forward in the building of the UHV DC converter station, need to learn detuning protection frequently transmitting events, real-time detection condition of the AC system harmonic voltage, closely monitor the DC bias influence on grid, trying to identify hidden trouble to eliminate defects. Suggestions for frequent case detuning protection, in-depth study in converter transformers charging the influence of harmonic excitation inrush current of AC system.
中图分类号 TM714
所属栏目 直流运检
基金项目
收稿日期 2013/8/4
修改稿日期
网络出版日期
作者单位点击查看
备注施红军(1976-),男,工程师,本科,从事继电保护调试及变电站设备安装管理工作。
引用该论文: Shi Hongjun,Feng Jian,Jia Xuantao. Impact of UHV DC Transmission AC Filter Detuning Protect the Accuracy of the Analysis[J]. Power & Energy, 2013, 34(5): 475~477
施红军,冯舰,贾轩涛. 影响特高压直流输电交流滤波器失谐保护准确性的分析[J]. 电力与能源, 2013, 34(5): 475~477
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】郑劲.特高压直流输电工程的谐波限制标准及滤波器的设计[J].电网技术,2007,31(13): 5-10.
【2】吴方劼.特高压换流站交流滤波器现场试验的分析与探讨[J].高电压技术,2010,36(1): 172-177.
【3】黄华.变压器直流偏磁的振动特性研究[J].华东电力2009,37(1):139-142.
【2】吴方劼.特高压换流站交流滤波器现场试验的分析与探讨[J].高电压技术,2010,36(1): 172-177.
【3】黄华.变压器直流偏磁的振动特性研究[J].华东电力2009,37(1):139-142.
相关信息