Research on Neutral Ground Design Proposals of Wind Farm 35 kV System
摘 要
大型风电场汇集线在发生单相接地故障时, 因电弧不能自熄而产生间歇性电弧或谐振引起的过电压, 造成电缆绝缘击穿、避雷器爆炸等故障, 给汇集线的安全、可靠运行带来严重后果。介绍了35 kV风电场汇集线中性点经消弧线圈接地及小电阻接地方式的设计方案和计算方法。通过应用案例分析, 交流了运行经验和注意事项, 可供优化设计提供参考。
Abstract
When the single-phase ground fault of the large wind farm collection line system was happened, the arc can not be self-extinguishing, thus resulting intermittent arcing or over-voltage caused by resonance, and it easily lead to cable insulation breakdown, explosion arrester failures, which cause serious consequences to the collection line security and reliability. This article describes designs and methods of calculation of the 35 kV wind farm collection line arc-suppression-coil-ground neutral system and low resistance grounding system. The experiences and points of attentions were provided to the design optimization, through the analysis of actual cases.
中图分类号 TM862
所属栏目 能源技术
基金项目
收稿日期 2013/12/14
修改稿日期
网络出版日期
作者单位点击查看
备注吕仁帅(1971-),男, 工程师, 本科, 从事风电运行和维护管理。
引用该论文: Lü Renshuai,Zhao Peng,Yuan Shuai,Jia Jing. Research on Neutral Ground Design Proposals of Wind Farm 35 kV System[J]. Power & Energy, 2014, 35(1): 80~84
吕仁帅,赵 鹏,袁 帅,贾 晶. 风电场35 kV系统中性点接地设计方案分析[J]. 电力与能源, 2014, 35(1): 80~84