Cause of Leakage of Water Wall Tube of Boiler of a Hydropower Plant
摘 要
某水电厂锅炉水冷壁管发生泄漏,通过宏观观察、化学成分分析、扫描电镜分析、能谱分析以及显微组织观察等方法,分析了水冷壁管泄漏的原因。结果表明:水冷壁管发生泄漏的原因是高温烟气中的腐蚀性介质渗入墙体内部,导致水冷壁管发生腐蚀,管壁减薄,最终发生泄漏。
Abstract
A water wall tube leaked of boiler of a hydropower plant. Through macro observation, chemical composition analysis, scanning electron microscopy analysis, energy spectrum analysis and microstructure observation, the reason for leakage of water wall tube was analyzed. The results showed that the reason for leakage of water wall tube was that corrosive medium in high-temperature flue gas penetrated into the wall, causing water wall tube to corrode, tube wall was thinned, and finally leaked.
中图分类号 TG115 DOI 10. 11973/lhjy-wl202111016
所属栏目 质量控制与失效分析
基金项目
收稿日期 2020/9/28
修改稿日期
网络出版日期
作者单位点击查看
备注付洋洋(1989-),男,工程师,主要从事金相检验及失效分析工作,nlfd_lg@163.com
引用该论文: FU Yangyang. Cause of Leakage of Water Wall Tube of Boiler of a Hydropower Plant[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2021, 57(11): 63~65