Reasons for leakage of sampling pipe elbow of high temperature reheat steam drain tank level gauge
摘 要
某电厂高温再热蒸汽疏水罐液位计取样管道弯管在运行中发生泄漏。采用宏观观察、化学成分分析、金相检验、硬度测试等方法,对弯管泄漏的原因进行了研究。结果表明:该弯管发生了应力腐蚀开裂,制造弯管时的热处理工艺控制不当,且内壁下部积水提供了腐蚀环境,最终导致弯管发生开裂并泄漏。
Abstract
The elbow of the sampling pipe for the high temperature reheat steam drain tank level gauge in a power plant leaked during operation. The causes of elbow leakage were studied using macroscopic observation, chemical composition analysis, metallographic examination and hardness testing. The results shows that stress corrosion cracking occurred in the elbow, improper control of the heat treatment process during the manufacturing of the elbow, and accumulation of water at the lower part of the inner wall provided a corrosive environment, ultimately led to cracking and leakage of the elbow.
中图分类号 TB31 TG142.1 DOI 10.11973/lhjy-wl202305010
所属栏目 质量控制与失效分析
基金项目
收稿日期 2022/8/1
修改稿日期
网络出版日期
作者单位点击查看
备注王飞(1972-),男,本科,高级工程师,主要从事火电厂金属技术监督工作,wangfei7211@sina.com
引用该论文: WANG Fei,YANG Chao,WU Wei,WU Zengyi,SHI Renqiang. Reasons for leakage of sampling pipe elbow of high temperature reheat steam drain tank level gauge[J]. Physical Testing and Chemical Analysis part A:Physical Testing, 2023, 59(5): 40~43
王飞,杨超,吴伟,吴增祎,石仁强. 高温再热蒸汽疏水罐液位计取样管道弯管泄漏原因[J]. 理化检验-物理分册, 2023, 59(5): 40~43
共有人对该论文发表了看法,其中:
人认为该论文很差
人认为该论文较差
人认为该论文一般
人认为该论文较好
人认为该论文很好
参考文献
【1】王然,贺明贤.热处理对T91钢金相组织及显微硬度的影响[J].金属热处理,2000,25(11):6-8.
【2】金国明,郭雅丽.常见弯管缺陷与预防措施[J].模具技术,1999(4):64-67.
【3】毛苗,江楠.90°厚壁弯管的应力分析与试验研究[J].压力容器,2010,27(7):5-8.
【4】马爱梅,陈红艳.基于有限元的弯管应力分析研究[J].机械设计,2004,21(增刊1):32.
【2】金国明,郭雅丽.常见弯管缺陷与预防措施[J].模具技术,1999(4):64-67.
【3】毛苗,江楠.90°厚壁弯管的应力分析与试验研究[J].压力容器,2010,27(7):5-8.
【4】马爱梅,陈红艳.基于有限元的弯管应力分析研究[J].机械设计,2004,21(增刊1):32.
相关信息