Overview of the Key Points and New Technologies of Generator Stator Cooling Water Treatment

More Information
  • Received Date: December 14, 2017
  • In view of the corrosion problem existing in generator stator hollow copper coil, the importance of controling the cold water quality and the main influencing factors of the stator copper coil corrosion are introduced, several main treatment methods and intelligent water distribution methods for the current generator stator cooling water are discribed, and each method is evaluated. In the operation of generator stator cooling water system, the pH and oxygen content of the cooling water should be stable for a long time, and the carbon dioxide concentration should be less than 1.5×10-5 mol/L. The application effects of intelligent water distribution methods of generator stator cooling water are good water quality, low operating cost, stable and reliable long-term operation, and thus assuring the water quality being always within the best anti-corrosion range.
  • [1]
    王溯. 发电机内冷水系统防腐蚀研究[D]. 长沙:长沙理工大学, 2010.
    [2]
    孙本达, 马智敬. 超超临界机组发电机内冷却水运行中存在的问题及处理[J]. 热力发电, 2009, 38(1):96-98.
    [3]
    关玉芳, 楼新明, 冯礼奎, 等. 发电机定子线棒堵塞治理与定冷水水质优化[J]. 浙江电力, 2012, 31(3):31-34.
    [4]
    谢学军, 吕珂, 晏敏, 等. 铜水体系电位-pH图与发电机内冷水pH调节防腐[J]. 腐蚀科学与防护技术, 2007, 19(3):162-163.
    [5]
    PAN L, HAN Q Q, XIE X N, et al. Corrosion prevention of the generator stator hollow copper conductor and water quality adjustment of its internal cooling water[J]. Energy and Power Engineering, 2009, 1(1):17-20.
    [6]
    MATTHIAS S, THOMAS B. Changing stator cooling water chemistry[J]. Power Plant Chemistry, 2014. 16(6):344-351.
    [7]
    ROBERT S. Review of alkaline treatment for generator stator cooling water systems[J]. Power Plant Chemistry, 2014, 16(6):352-359.
    [8]
    EPRI. Prevention of flow restrictions in generator stator water cooling circuits[R].[S.L.]:EPRI,2002.
    [9]
    肖子丹, 王溯, 杨道武, 等. 二氧化碳对发电机内冷水pH与电导率的影响[J]. 工业水处理, 2011, 31(2):25-28.
    [10]
    曹顺安, 封冰清, 张芮源, 等. 发电机内冷水处理机理与技术综述[J]. 工业水处理, 2016, 36(5):15-19.
    [11]
    孙本达, 刘涛, 张广文, 等. 一种新的发电机内冷却水处理技术[J]. 热力发电, 2011, 40(10):78-80, 84.
    [12]
    谢学军, 晏敏, 胡明玉, 等. 发电机内冷水处理方式探讨[J]. 腐蚀科学与防护技术, 2006, 18(4):273-277.
    [13]
    范圣平, 苏伟, 曹顺安, 等. 发电机内冷水处理技术研究进展[J]. 广东电力, 2015, 28(4):7-11.
    [14]
    时准. 基于正交试验的发电机定子线圈冷却水pH控制研究[D]. 上海:上海交通大学, 2014.
    [15]
    苗冬梅. 达电发电机内冷水净化处理系统的应用[J]. 科技风, 2014(20):90-90.