Page 123 - 电力与能源2024年第二期
P. 123
第 45 卷 第 2 期 电力与能源
2024 年 4 月 263
DOI:10.11973/dlyny202402027
二次设备端子排接触不良检测技术研究
周徐达
(国网上海市电力公司超高压分公司,上海 200063)
摘 要:二次设备端子排接触不良一般很难引起重视,而一旦出现接触不良等异常,很可能导致保护设备不正
确动作。目前,对于端子排接触不良检测还是依靠人工拉线扯线,效率低下且难以保证质量。对此,本文提出
了一种专门针对二次设备端子排接触不良异常的检测方法,力求用更高效的方法检测端子排接触不良缺陷。
关键词:端子排;二次设备;接触不良;缺陷检测
作者简介:周徐达(1982—),男,从事直流输电、变电运维等方面工作。
中图分类号:TM75 文献标志码:A 文章编号:2095-1256(2024)02-0263-04
Poor Contact Detection Technology for Terminal Strips in Secondary Equipment
ZHOU Xuda
(State Grid Extra High Voltage Branch,SMEPC,Shanghai 200063,China)
Abstract:Detecting poor contact in terminal strips of secondary equipment does not attract enough attention.
However,once abnormal contact occurs,it can lead to incorrect operation of protection equipment. Currently,
manual wire pulling is still the main method for detecting poor contact in terminal strips,which is inefficient and
does not guarantee quality. This paper proposes a detection method specialized for abnormal contacts in terminal
strips of secondary equipment and aims to address the inefficiencies associated with poor contact using more effec⁃
tive methods.
Key words:terminal strip,secondary equipment,poor contact,defect detection
二次设备系统复杂,存在很多常规校验无法 从而阻碍设备的正常操作。因此,研究和研发针
发现的隐患,特别是关于二次设备传输与辅助环 对变电站端子排接触不良的有效防控与检测技术
节的潜在问题,如回路端子排接触不良等。目前 意义重大 [6-8] 。
针对此类问题的检验手段十分有限,难以对其运
1 端子排常见缺陷分析
行水平进行评估,却非常容易引发突发事故 [1-2] 。
对于通信回路、模拟量传输回路接触不良、开路导 1.1 端子排缺陷原因
致的隐患等都很难定期进行性能验证。在变电站 二次回路端子经长时间运行后会因应力变化
中,二次设备的电回路主要由各功能元件及其连 或外部原因造成二次电缆接线松动,目前对于端
接的二次电缆组成,而安装于各屏柜的各种端子 子排接线松动的检测通常采用人工直接试拉的方
排作为二次回路的重要部件,起着对二次回路接 法,该方法只能适用于设备停电状态,且线松紧的
线进行分段、转接的作用。它不仅使屏柜内众多 感受度因人而异,缺乏标准 [9-10] 。
回路得以分类整齐地引出,还为屏柜间的接线提 此外,在技改、设备换新的作业中,人工紧线
供了便利的操作点,便于对二次回路进行分段维 工作量较大,多次出现因螺丝刀用力不当引起的
护和故障排查 [3-5] 。 工具与端子排损坏事故,因此配备具有自测力矩
在日常的二次设备的检查与维护工作中,经 的紧线工作十分必要。变电站二次设备端子数量
常会遇到端子排故障导致的二次设备回路缺陷, 极多,然而目前还是主要依靠手拉动二次线来检